EAN code8595057639911
Customs code83024190
Weight2,4000 kg/pcs
Surface finishHot Dip Galvanized
Funcionality in fireP90-R, E90, PS90
Fire resistance standardsČSN 73 0895, DIN 4102-12, STN 92 0205
Maximum load200 kg
Dimension A1020 mm
Dimension B155 mm
Dimension C90 mm
For width of cable tray1000 mm
For height of cable tray35 - 110 mm
Max. load for fire resistance10 - 20 kg

The holder is designed to be mounted on a wall or a ceiling profile. For assembly to the ceiling profile SPL and SPS there are used the sliding nuts PM 41 M 10 together with the bolts S 10X20 (2 pcs). Fix to the celling profile SPLN, SPSN or SPU using bolts S 10X20, nuts M 10 and washer PD 10. Cable tray attaching to the bracket DT is carried out by bolts NSM 6X10.

Note for system with maintained functionality in fire:
You find more information in the catalogue Systems with maintained functionality in fire.