EAN code | 8595057618695 |
Customs code | 73063041 |
Weight | 1,7300 kg/m |
Colour | black |
Material | steel |
Surface finish Varnished: Galvanized steel Sendzimir powder coated, color RAL 9005 black, medium corrosion resistance - Group 2 | |
Temperature resistance | -60 - 250 °C |
Mechanical resistance | 1250 N/5cm |
Mechanical protection | IK10 |
Length | 3 m |
Outside diameter | 47 mm |
Inner diameter (min.) | 44 mm |
Funcionality in fire | P90-R, E90, PS90 |
Thread type | P36 |
Sorting code | 44561 |
Standards | ČSN EN 61386-1 ed.2 |
Fire resistance standards | ČSN 73 0895, DIN 4102-12, STN 92 0205 |
Max. load for fire resistance | 10 kg |
The pipes are suitable for mechanical protection of conductors and cables. Threaded conduits are supplied with one coupler. While using pipes along with bushing 4813/P - 4842/P and 4913 - 4942 is scope of application only -5 - +60 °C.
Note for system with maintained functionality in fire:
max. 1 piece of cable in the pipe
You find more information in the catalogue Systems with maintained functionality in fire.